Adaptive Distance Protection for Transmission Lines Incorporating SSSC with Energy Storage Device
Document Type
Article
Publication Title
IEEE Access
Abstract
A Static Synchronous Series Compensator incorporating energy storage device (SSSC-ES) at the DC bus enables the exchange of true power with the system in addition to line reactance compensation. This facilitates improved control of real and reactive power in a transmission system. However, the four-quadrant operation of SSSC presents additional problems for the accurate operation of conventional transmission line protection. In this paper, an in-depth analysis of the effect of emulated reactance and resistance by SSSC-ES installed at the center of a hybrid series compensated line on the performance of distance relay is carried out. An investigation is performed with all possible operating modes and control strategies of SSSC-ES, and the possibility of mal-operation of distance protection are explored. A novel adaptive setting based on constant reactance and constant resistance emulation control strategy of SSSC is proposed for quadrilateral distance relay to prevent the mal-operation. MATLAB / SIMULINK is used for the simulation study.
First Page
156017
Last Page
156026
DOI
10.1109/ACCESS.2020.3019173
Publication Date
1-1-2020
Recommended Citation
Gururaja Rao, H. V.; Prabhu, Nagesh; and Mala, R. C., "Adaptive Distance Protection for Transmission Lines Incorporating SSSC with Energy Storage Device" (2020). Open Access archive. 1808.