"Adaptive Distance Protection for Transmission Lines Incorporating SSSC" by H. V. Gururaja Rao, Nagesh Prabhu et al.
 

Adaptive Distance Protection for Transmission Lines Incorporating SSSC with Energy Storage Device

Document Type

Article

Publication Title

IEEE Access

Abstract

A Static Synchronous Series Compensator incorporating energy storage device (SSSC-ES) at the DC bus enables the exchange of true power with the system in addition to line reactance compensation. This facilitates improved control of real and reactive power in a transmission system. However, the four-quadrant operation of SSSC presents additional problems for the accurate operation of conventional transmission line protection. In this paper, an in-depth analysis of the effect of emulated reactance and resistance by SSSC-ES installed at the center of a hybrid series compensated line on the performance of distance relay is carried out. An investigation is performed with all possible operating modes and control strategies of SSSC-ES, and the possibility of mal-operation of distance protection are explored. A novel adaptive setting based on constant reactance and constant resistance emulation control strategy of SSSC is proposed for quadrilateral distance relay to prevent the mal-operation. MATLAB / SIMULINK is used for the simulation study.

First Page

156017

Last Page

156026

DOI

10.1109/ACCESS.2020.3019173

Publication Date

1-1-2020

This document is currently not available here.