Experimental Investigation on Dehumidification Using a Solid Composite Bio Desiccant Internally Cooled Using Nanofluids for Building Cooling
Document Type
Article
Publication Title
Buildings
Abstract
Indoor comfort has become a major factor with advancements in science and technology. This also leads to an increase in greenhouse gases as well as energy consumption. Desiccant-coated heat exchangers are one of the common solutions to these risks and to lower energy usage. In the present work, the capability of a solid composite desiccant blend prepared from coconut shell-based activated carbon and bio char was studied. Aluminum plates have been coated with the prepared solid desiccants. Desiccant-coated heat exchangers were cooled by the cerium oxide nanofluid passing through the pipes connected along the length of the heat exchanger. Air was blown through the plates where dehumidification occurs due to the vapor pressure difference between the air and the desiccant-coated plate. The experiments were conducted by varying the air velocity, water flow rate, and nanoparticle concentration. The nanoparticle volume fraction varied from 0.05% to 0.3%. Different performance parameters such as the moisture removal rate, dehumidification efficiency, cooling capacity, and coefficient of performance (COP) were calculated. Results showed that the performance parameters were enhanced with an increase in the water flow rate as well as the air flow rate. Furthermore, it was seen that with the addition and increase in nanoparticle concentration, the moisture removal rate and dehumidification efficiency were enhanced. In comparison to no addition of nanoparticles, a 0.3% addition of nanoparticles demonstrated a maximum increase in MRR of 53% and dehumidification efficiency of 57%. A maximum reduction of 6.1% in the dehumidification area was achieved by using 0.3% nanoparticles with water. It is recommended to use nanofluids for dehumidification using solid desiccants, which can enhance the performance without having negative influence on the environment.
DOI
10.3390/buildings13061461
Publication Date
6-1-2023
Recommended Citation
Kumar, Shiva; Hariharan, Girish; Fayaz, Muhammad; and Kumar, Nitesh, "Experimental Investigation on Dehumidification Using a Solid Composite Bio Desiccant Internally Cooled Using Nanofluids for Building Cooling" (2023). Open Access archive. 5548.
https://impressions.manipal.edu/open-access-archive/5548